4.2 CORRUGATED |
|
|
|
ROOFING: POSITIVE
LOADS |
SPAN |
Uniform
Loads,
PSF |
SERIE |
FR200 |
FR300 |
FR400 |
FM
10 |
FM
13 |
FM
16 |
SINGLE |
20 |
4'8" |
5'6" |
5'10" |
4'6" |
5'0" |
5'5" |
TWO |
6'4" |
7'5" |
7'10" |
6'1" |
6'9" |
7'3" |
THREE |
5'10" |
6'10" |
7'3" |
5'7" |
6'2" |
6'8" |
SINGLE |
25 |
4'4" |
5'1" |
5'5" |
4'2" |
4'8" |
5'0" |
TWO |
5'10" |
6'11" |
7'4" |
5'8" |
6'3" |
6'9" |
THREE |
5'5" |
6'4" |
6'9" |
5'2" |
5'9" |
6'2" |
SINGLE |
30 |
4'1" |
4'10" |
5'1" |
3'11" |
4'4" |
4'9" |
TWO |
5'6" |
6'6" |
6'10" |
5'3" |
5'10" |
6'4" |
THREE |
5'1" |
6'0" |
6'4" |
4'11" |
5'5" |
5'10" |
SINGLE |
35 |
3'11" |
4'7" |
4'10" |
3'9" |
4'2" |
4'6" |
TWO |
5'1" |
6'2" |
6'6" |
5'0" |
5'7" |
6'0" |
THREE |
4'10" |
4'8" |
6'0" |
4'8" |
5'1" |
5'6" |
SINGLE |
40 |
3'9" |
4'4" |
4'8" |
3'7" |
3'11" |
4'3" |
TWO |
4'9" |
5'11" |
6'3" |
4'10" |
5'4" |
5'9" |
THREE |
4'7" |
5'5" |
5'9" |
4'5" |
4'11" |
4'4" |
SINGLE |
50 |
3'5" |
4'1" |
4'4" |
3'4" |
3'8" |
4'0" |
TWO |
4'3" |
4'4" |
4'9" |
4'5" |
4'11" |
5'4" |
THREE |
4'3" |
5'0" |
5'4" |
4'1" |
4'7" |
4'11" |
|
|
ROOFING: NEGATIVE
LOADS
Fasteners required at every other corrugation |
SPAN |
Uniform
Loads,
PSF |
SERIE |
FR200 |
FR300 |
FR400 |
FM
10 |
FM
13 |
FM
16 |
SINGLE |
20 |
4'8" |
5'6" |
5'10" |
4'6" |
5'0" |
5'5" |
TWO |
6'4" |
7'5" |
7'10" |
6'1" |
6'9" |
7'3" |
THREE |
5'10" |
6'10" |
7'3" |
5'7" |
6'2" |
6'8" |
SINGLE |
25 |
4'4" |
5'1" |
5'5" |
4'2" |
4'8" |
5'0" |
TWO |
5'10" |
6'11" |
7'4" |
5'8" |
6'3" |
6'9" |
THREE |
5'5" |
6'4" |
6'9" |
5'2" |
5'9" |
6'2" |
SINGLE |
30 |
4'1" |
4'10" |
5'1" |
3'11" |
4'4" |
4'9" |
TWO |
5'6" |
6'6" |
6'10" |
5'3" |
5'10" |
6'4" |
THREE |
5'1" |
6'0" |
6'4" |
4'11" |
5'5" |
5'10" |
SINGLE |
35 |
3'11" |
4'7" |
4'10" |
3'9" |
4'2" |
4'6" |
TWO |
5'1" |
6'2" |
6'6" |
5'0" |
5'7" |
6'0" |
THREE |
4'10" |
4'8" |
6'0" |
4'8" |
5'1" |
5'6" |
SINGLE |
40 |
3'9" |
4'4" |
4'8" |
3'7" |
3'11" |
4'3" |
TWO |
4'9" |
5'11" |
6'3" |
4'10" |
5'4" |
5'9" |
THREE |
4'7" |
5'5" |
5'9" |
4'5" |
4'11" |
4'4" |
SINGLE |
50 |
3'5" |
4'1" |
4'4" |
3'4" |
3'8" |
4'0" |
TWO |
4'3" |
4'4" |
4'9" |
4'5" |
4'11" |
5'4" |
THREE |
4'3" |
5'0" |
5'4" |
4'1" |
4'7" |
4'11" |
|
|
SIDING: WIND LOADS
Fasteners required at every other corrugation |
SPAN |
Uniform
Loads,
PSF |
SERIE |
FR150 |
FR200 |
FR300 |
FR400 |
FM
10 |
FM
13 |
FM
16 |
SINGLE |
20 |
5'4" |
5'11" |
7'0" |
7'5" |
4'8" |
6'4" |
6'10" |
TWO |
6'7" |
7'10" |
9'2" |
9'7" |
7'8" |
8'6" |
9'0" |
THREE |
6'7" |
7'4" |
8'7" |
9'0" |
7'1" |
7'10" |
8'5" |
SINGLE |
25 |
4'11" |
5'6" |
6'6" |
6'10" |
5'3" |
5'10" |
6'4" |
TWO |
5'11" |
7'0" |
8'8" |
9'1" |
7'1" |
7'10" |
8'6" |
THREE |
6'2" |
6'9" |
8'0" |
8'6" |
6'6" |
7'3" |
7'10" |
SINGLE |
30 |
4'8" |
5'2" |
6'1" |
6'5" |
5'0" |
5'6" |
5'11" |
TWO |
5'5" |
6'4" |
8'2" |
8'8" |
6'8" |
7'5" |
8'0" |
THREE |
5'9" |
6'5" |
7'6" |
8'0" |
6'2" |
6'10" |
7'4" |
SINGLE |
35 |
4'5" |
4'11" |
5'9" |
6'2" |
4'9" |
5'3" |
5'8" |
TWO |
5'0" |
5'11" |
7'9" |
8'3" |
6'0" |
7'0" |
7'7" |
THREE |
5'6" |
6'1" |
7'2" |
7'7" |
5'10" |
6'6" |
7'0" |
SINGLE |
40 |
4'3" |
4'8" |
5'6" |
5'10" |
4'6" |
5'0" |
5'5" |
TWO |
4'8" |
5'6" |
7'5" |
7'10" |
5'3" |
6'9" |
7'3" |
THREE |
5'3" |
5'10" |
6'10" |
7'3" |
5'7" |
6'2" |
6'8" |
SINGLE |
50 |
3'11" |
4'4" |
5'1" |
5'5" |
4'2" |
4'8" |
5'0" |
TWO |
3'11" |
4'6" |
6'4" |
3'3" |
4'3" |
5'5" |
6'8" |
THREE |
4'5" |
5'2" |
6'4" |
6'9" |
4'10" |
5'9" |
6'2" |
|
Load/Span Tables are based on full
scale tests that consider three design parameters:
- Critical bending moment at actual
panel failure
- Flexural stiffness
- Pullover force per fastener of the
panel section.
Table values are based upon:
- Roofing: Deflection l/60, FOS
2.5+, 1.88-
- Siding: Deflection L/30 FOS
1.88
|
|
|
|
|
The load/span tables shown in this
Guide are derived large scale tests using full panels to simulate actual service
conditions (at a reference temperature of 77° F). These tests include two span vacuum box
test and three point load tests.
Each span shown in the load/span tables represents the most conservative span derived when
the panel is assessed using the following parameters:
Design Parameters
- Critical bending moment at actual
panel failure;
- Flexural stiffness factor, EI, (where
E is the flexural
modulus of elasticity and I is the moment of inertia of
the panel section); and
- Pullover force resistance per
fastener.
|
|
|
The load/span tables shown in this
Guide are developed using the following maximum deflections limits and Factors of Safety
(FOS), unless otherwise noted:
Panel Roofing:
Positive Loads: Deflection: L/60, FOS:2.5
Negative Loads: Deflection: L/60, FOS: 1.88
Panel Siding:
Wind Loads: Deflection: L/30, FOS:1.88
Roof Deck:
Dead + Live Loads: Deflection: L/180, FOS:2.5 Uplift Loads: Deflection: L/18000, FOS:1.88
The load/span tables are to be used as a guide only as specific environmental conditions
are not considered.
Specific applications should be verified by a registered
Professional Engineer. |